KFR50/51/53/55/56 : ¼ and ½ inch
KFR63/66/74/75 : 3/8 and 5/8 inch
KMS3MIO :
9000 BTU & 12000 BTU – ¼ and 3/8 inch
18000 BTU – ¼ and ½ inch (valve size is 3/8 inch; one adaptor is required)
KMS5MIO :
9000 BTU & 12000 BTU – ¼ and 3/8 inch
18000 BTU – ¼ and ½ inch (valve size is 3/8 inch; one adaptor is required)
KFR120 : liquid pipe 3/8 inch¸ gas pipe 5/8 inch
All are pre charged for 6 metres of pipes; any longer and refrigerant MUST be added (see question 4 below). If the unit requires more refrigerant, this will have to be added by an FGAS registered engineer.
KFR23/26/33/36 : for each additional metre of pipe-work over 6 metres add 30g per metre.
KFR50/53/55/56 : for each additional metre of pipe-work over 6 metres add 40g per metre.
KFR63/66/74/75/120 : for each additional metre of pipe-work over 6 metres add 50g per metre.
KMS3MIO :
9000 BTU – for each additional metre of pipe-work over 6 metres add 30g per metre of gas.
18000 BTU – for each additional metre of pipe-work over 6 metres add 50g per metre of gas.
KMS5MIO :
12000 BTU – for each additional metre of pipe-work over 6 metres add 40g per metre of gas.
18000 BTU – for each additional metre of pipe-work over 6 metres add 50g per metre of gas.
Please note any extra refrigerant will need to be added by an FGAS registered engineer. If you need help sourcing a local engineer, give us a call on 03703344556.
KFR23/26/33/36/37 : 15 metres
KFR50/53/55/56/57 : 20 metres
KFR63/66/74/75 : 25 metres
KMS3MIO :
9000 BTU – 20 metres
18000 BTU – 20 metres
NOTE: maximum total pipe run for all connected units is 50 metres.
KMS5MIO :
12000 BTU – 20 metres
18000 BTU – 20 metres
NOTE: maximum total pipe run for all connected units is 80 metres.
KFR120 : 30 metres
KFR120 requires a 20 Amp supply with a C or D Motor Rated Trip/Fuse
NOTE: Ceiling Cassette Models KFR50/74/120 require power to both indoor and outdoor units.
KMS3MIO require a standard 13 Amp supply / spur to the outdoor unit; the outdoor unit supplies power to the indoor units.
KMS5MIO require a standard 20 Amp supply / spur with a C or D Motor Rated Trip/Fuse to the outdoor unit; the outdoor unit supplies power to the indoor units.
KFR23/26/33/36/53/56/63/66 require mains power supply to the INDOOR UNIT ONLY.
KFR37/50/55/57/74/75/120/ require mains power supply to both indoor and outdoor units.
KMS3MIO/5MIO and matching indoor units require power supply to the OUTDOOR UNIT ONLY.
Based on an average cost of electricity @ 10p per kilowatt hour (divide the figures by .10 and multiply by you Kwh price to get an accurate figure)
Inverter models cost approx 20% less to run on average.
KFR32 – 10.53p per hour
KFR51 – 16.36p per hour
KFR66 – 21.62p per hour
KFR50 – 18.94p per hour
KFR70 – 28.92p per hour
KYR35 – 13.99p per hour
THP06 – 10p per hour
THP09 – 14p per hour
THP12 – 18p per hour
KYR25 : 17 to 30 degrees Celsius
KYR35/45, KFR37/50/55/57/74/75/120 : 17 to 31 degrees Celsius.
All systems operate from -15 to +45°C.
Heating:
KMS3MIO/5MIO, KFR37/50/55/57/74/75/120 operate from -15 to +45°C.
KFR23/26/33/36/53/56/63/66 operate from -10 to +45°C.
Multi-split units come with an indoor and outdoor unit¸ electrical interconnecting cables¸ a wall mounting bracket for the indoor unit and a remote control¸ plus manuals.
Ceiling Cassettes come with an indoor and outdoor unit¸ pre-insulated copper pipe-work to connect the units¸ electrical interconnecting cables¸ ceiling trim panel for the indoor unit¸ ceiling fixings (subject to ceiling void height) and a remote control¸ plus manuals.
Mobile Air Conditioner units come with an exhaust hose¸ window fitting kit for exhaust hose¸ water outlet pipe and a remote control¸ plus manuals.
As a guide if you have a warehouse of a minimum 2000 approx SqFt with high eaves then this would be acceptable for the outdoor unit¸ but more units would need a larger warehouse¸ approx extra 1000 SqFt per unit. The warehouse temperature would also need to be fairly cool¸ as most are but it would not be suitable in a hot manufacturing area for example.
However we would recommend as part of the general maintenance of the whole system that it is periodically treated for rust and anti-corrosion.
If you are in an area where the air has a higher salt content then we suggest that a higher level of maintenance is carried out to increase the life of the casing.
A ‘picket fence’ type of surround i.e. planked with very open gaps with a roof would be acceptable. The front must have at least 60cm clear and the back 10cm or the ‘planks’ must give at least 50% air flow between them.
This is due to the location of the louvers along the bottom of the inside unit as it is designed to mount high on the wall and blow down into the room.
However¸ many customers have done this with good results; keep louvers fixed horizontally and do not block the flow into the room.
As a rule you will lose about 15% efficiency. In winter it actually works very well as heat rises!
The timer function works on a day to day basis. The settings are stored in the remote control unit and sent to the indoor unit through infrared signalling. You just initialise the timer each day by pointing the remote at the indoor unit and pressing the timer function.
General Maintenance:
The inside unit will require the filters to be checked and possibly removed¸ cleaned and refitted at least once a quarter depending on how dusty the environment is. Contact us for help on removing and refitting the filters if you are unsure.
Annual Servicing:
In line with the manufacturers recommendations¸ and to keep any warranty validated¸ your system must have an annual service from a qualified FGAS registered air conditioning engineer who will check temperatures of the coils¸ check the pipework and to clean the internal and external coils and foil fins.
DO NOT USE the equipment again until you are told to do so by our engineers otherwise permanent damage may occur.
However there are two exceptions to this rule¸ they are ‘DF’ or ‘#‘ (dependant on system model)¸ Both these codes mean that the unit is running through it’s defrost procedure and normal operation will resume within approx 30mins. This normally only happens during the colder months. If your system does not resume operation please contact us.
A pump must be used when it is not possible to use gravity to take the condensation water away from the drip tray in the indoor unit to the outside of the premises.
The pump is placed inside the drip tray or above the ceiling and will pump the water up to a maximum height of 8 metres¸ then out of the building.
A Mini Lime Pump like the Orange Pump is used to take the condensation water from the drip tray; however it is fitted in plastic conduit (trunking) to the side of the indoor unit rather than fitted into the drip tray. You can use this conduit to hide your refrigerant pipes and cables as well. It can take the condensation water upwards a maximum height of 8 metres.
Please note other pumps are available, give us a call on 03703344556 to discuss.
3.6m (10.8ft) maximum length for KYR-25CO.
4m (12ft) maximum length for KYR-35/45.
Window Kit:
For KYR-25 the maximum extension length is 95cm.
For KYR-35/45 the maximum extension length is 106.5cm.
The drain hose dimensions of the PDH series Dehumidifiers are:
500mm length
17mm ø Hose end connection to the appliance
15mm ø Outlet to drain connection
The additional charge for R32 is as below:
1/4 liquid pipe over 6m = 15g per meter
3/8 liquid pipe over 6m = 30g per meter